Reference Library - Peroxide Applications : Municipal Wastewater


SURFACE WATER TREATMENT

residual ozone destruction




Ozone treated drinking water can contain small quantities of residual ozone that may be released into the atmosphere in certain water treatment plant stages, e.g. mix tanks, filters, etc. OxyPureTM hydrogen peroxide can be added to ensure destruction of residual ozone and minimize ozone release.

H2O2 + O3 ----> 2 . OH + 3/2 O2 ----> H2O + 2 O2


For 1 mg/L ozone, 1.4 mg/L 50% OxyPureTM must be added.


Advantages




[Back to Municipal Drinking Water Applications] | [Forward to Next Article]